AUXILIARY BOILER ALARM TESTING ONBOARD
Auxiliary boiler alarm testing onboard is part of the PMS (Planned Maintenance System) which is done on a monthly basis. Alarm testing is one of the important maintenance activity on board as it helps in keeping them in good condition and helping not to cause any kind of breakdown on the auxiliary boiler. It also helps in avoiding any hazards or accidents on the auxiliary boiler. There are many kinds of alarms which are to be tested on the auxiliary boiler which are mentioned below. Some of them also lead to the trip or shutdown of the auxiliary boiler. Testing of alarms for auxiliary boiler also helps in checking the calibration of the transmitter, probe or the float switch that it is working properly or not & it is triggering the alarm for the auxiliary boiler at the set parameter.
Low Oil Pressure in Burner alarm
Close valve to pressure switch in H.P. F.O. line
Start boiler manually
Alarm will sound
Re-open the valve to pressure switch
Low Oil Pressure in ring line alarm
Run boiler manually
Switch stand-by Auxiliary Boiler F.O. Supply pump off
Switch running Auxiliary Boiler F.O. Supply pump off
Alarm will sound
Restart before running pump and switch other pump back to stand-by
Flame Failure alarm
Run boiler manually
Pull out the flame eye
Alarm will sound
Insert flame eye
Boiler trip alarm
Switch standby Auxiliary Boiler F.O. Supply pump off
Switch running Auxiliary Boiler F.O. Supply pump off
Alarm will sound
Restart before running pump and switch other pump back to stand-by
Low Water Level alarm (-160 mm)
Close valve before feed water valve
Close valves V8 (upper and lower) to differential pressure transmitter
Slowly open drain valve next to transmitter (near burner unit) on Low level side (left)
Alarm will sound
Close drain valve and open valves again
Open valve before feed water valve
High Water Level alarm (+ 360 mm)
Close upper valve to differential pressure transmitter
Slowly open drain valve next to transmitter on High level side (right)
Alarm will sound
Close the drain valve again
Open upper valve
Low-Low Water Level alarm (SB float level switch)
Close valve before feed water valve
Close lower and upper valve to SB float level switch
Slowly open drain under level switch
Alarm will sound
First open lower valve again and than upper valve
Open valve before feed water valve
Low-Low Water Level alarm (PS float level switch)
PS level switch and the low low level from the differential pressure transmitter are connected in series. So set differential pressure transmitter below -160 mm and the drain the PS float level switch. Then the boiler will trip on the low low level alarm.
Low Steam Pressure alarm
Close valve before pressure transmitter on gauge board
Loosen nut on the drain valve
Alarm will sound
Fasten the nut and open the valve again
Burner Motor Overload alarm
Open cabinet
Slide test button on contactor (under transparent plastic) to the left
Alarm will sound
Press black RESET button
Oil Booster Pump Overload
Slide test button on contactor (under transparent plastic) to the left
Alarm will sound
Press black RESET button
High Oil Temperature alarm (Aconis)
Take out PT-100 probe
Insert into probe tester
Set probe tester to 160˚C
Alarm will sound on Aconis
Take probe from tester and insert in socket again
Low Oil Temperature alarm
Take out PT-100 probe
Alarm will sound after a while on Aconis
Insert probe in socket again
Burner Swing Out alarm
Unscrew the limit switch at burner door
Alarm will sound
Put switch back in place
High Salinity in Feed Water
Make sure the Feed Water Pump Stop By-Pass is switched to ON (otherwise Feed Water Pumps stops when alarm is triggered)
At the hotwell, set the alarm value to a lower setpoint
Alarm will sound
Reset the alarm value to the normal setpoint
High Oil Content in Feed Water
Make sure the Feed Water Pump Stop By-Pass is switched to ON (otherwise Feed Water Pumps stops when alarm is triggered)
At the hotwell, on top of the Inspection Tank, open the cover of the sensor and increase the sensitivity (yellow potentiometer) until the Red LED is off
Alarm will sound
Reset the alarm value to the normal setpoint